Itnet Technologies
Expertise
Resources
About
Book a meeting
ITNET
ITNET Technologies
Online
Nola

Welcome!

Before we start, introduce yourself so Nola can better assist you.

France

Your data remains confidential

ITNET TECHNOLOGIES

Sovereign cloud - cybersecurity - datacenter

A technical partner for your critical digital environments.

ITNET TECHNOLOGIES designs, hosts and secures cloud, cybersecurity and datacenter infrastructure for organizations that require sovereignty, availability and operational control, with capacity operated in France and Finland.

Plan an IT auditExplore sovereign cloud

Business contact

Emailcontact@itnet-technologies.comPhone+33 3 39 10 96 21
Head office22 Rue de Pissefontaine, 78570 Chanteloup-les-Vignes
Dubai DIFC officeDubai International Financial Centre (DIFC), Dubai, United Arab Emirates
AvailabilityMon.-Fri. 09:00-18:00

Solutions

  • Sovereign cloud & secure hosting
  • Managed cybersecurity & audit
  • Immersion cooling
  • Direct Liquid Cooling
  • VOLTANEUM dielectric liquid
  • AXMARIL secret management

Trust

  • French company, data hosted in France or Finland depending on project scope
  • Architectures aligned with GDPR, NIS2 and ISO 27001 best practices
  • Monitoring and support for critical services
  • Infrastructure designed for performance and energy efficiency

Company

  • Book a meeting
  • Invest in ITNET
  • Resources & news

Legal

  • Legal notice
  • Privacy policy

Follow ITNET

LinkedInYouTubeX
SASU - SIRET 890 177 470 00014
Cloud, cybersecurity and sustainable infrastructure

Certifications, frameworks and technical assurances

Trust markers for your critical infrastructure.

Certifications & tools

Datacenter, security & compliance

© 2026 ITNET TECHNOLOGIES. All rights reserved.

Designed and operated by ITNET TECHNOLOGIES.

Back to BlogBlog

Power cables in immersion cooling: safety, materials and operations

Immersed power cabling requires strict qualification. Dielectric fluid helps, but electrical safety remains a complete discipline.

Mouhamed BANKOLEIT Infrastructure Expert
August 16, 20266 min read
Power cables in immersion cooling: safety, materials and operations

Search intent: understand how to choose and qualify power cables for immersion cooling without reducing safety to the dielectric fluid alone.

Power cabling and electrical distribution around an immersion cooling tank.
Power cabling and electrical distribution around an immersion cooling tank.

Power cables in immersion cooling: safety, materials and operations

Immersion cooling uses dielectric fluid, meaning the fluid is electrically insulating under its intended operating conditions. This property is essential, but it should not create a false sense of simplicity. Power cables, connectors, server power supplies, PDU, busbars and protection devices remain critical infrastructure components. They carry the energy that makes the platform run.

For readers designing a high-density datacenter or AI platform, the question is not only "can this cable be submerged?" The stronger question is: does this cable keep its mechanical, electrical and safety properties in this fluid, at this temperature, under this load, for this duration and under this maintenance procedure?

Voltaneum is directly concerned when GPU density increases electrical demand. Wayhost remains relevant for hosted services that depend on continuity. ITNET Technologies helps connect power, cooling, cybersecurity and operations into a coherent architecture.

Power Reference Table

Power cables must be sized according to local electrical codes, protection devices and supplier recommendations. The table below gives practical planning numbers to show why high-density servers quickly exceed ordinary cabling assumptions.

Supply Theoretical power 80% continuous load Practical reading
230 V single-phase 16 A 3.68 kW 2.94 kW insufficient for one dense GPU server
230 V single-phase 32 A 7.36 kW 5.89 kW tight for a high-end AI server
400 V three-phase 32 A 22.2 kW 17.7 kW suitable for a small server group
400 V three-phase 63 A 43.6 kW 34.9 kW coherent with a dense tank or zone
8 kW server at 230 V 34.8 A not applicable needs multiple feeds or adapted distribution

Concrete illustration: an 8 kW AI server cannot be treated like a conventional 1U server. At 230 V, it represents roughly 34.8 A. Even with dielectric fluid, power distribution, connectors, protection and maintenance must be designed for the real load.

Dielectric Fluid Does Not Replace Electrical Safety

Dielectric fluid reduces conduction risk in normal conditions, but it does not remove electrical design obligations. Protection, cable cross-section, connector ratings, grounding, selectivity, emergency shutdown, documentation and lockout procedure remain mandatory.

The risk profile changes. In immersion, teams must examine fluid compatibility with insulation, jacket behavior, connection points, mechanical strain and human intervention. A cable that softens, swells, cracks or loses identification can create a serious issue before a visible failure occurs.

Insulation, Jackets And Material Compatibility

Power cables use insulation and jackets that do not all react the same way to immersion fluids. Some materials may leach additives, change dimensions, lose flexibility or evolve mechanically. Compatibility must therefore be validated on the exact cable reference, not only on a generic cable family.

OCP immersion guidance emphasizes material compatibility and associated tests. Readers should ask for test conditions: fluid type, temperature, duration, mass or dimensional variation, visual inspection and acceptance criteria. Serious projects do not rely on a single marketing sentence.

Power Connectors And Connection Zones

The cable is only part of the issue. Connectors, contacts, locks, keying, seals, plastics and labels can be more sensitive than copper. In immersion, teams must know which elements sit in the fluid and which remain dry.

A good design avoids improvised connections above or near the tank. It defines clean routing, reasonable spare length, controlled bend radius, protected exits and durable identification. Connectors must be handled through a known procedure by trained staff, with traceability.

PDU, Busbars And High-Density Distribution

As GPU racks and tanks become denser, power distribution becomes central to design. PDU, busbars, protection devices and connection points should be planned with cooling, not bolted on later. Available power has little value if it cannot be distributed safely and maintained.

Some architectures move toward more integrated rack or tank-level distribution. Readers should verify mechanical, thermal and operational compatibility of the whole chain. OCP and ORV3 discussions show that power, cooling and interconnects are now interdependent.

Load, Temperature And Exposure Duration

A power cable must be qualified for its real load. Fluid temperature, circulation, cable grouping, local hot spots and mechanical constraints influence service life. A cable correctly sized in air should not be assumed equivalent inside a tank without analysis.

Qualification should include degraded scenarios: reduced pump flow, higher fluid temperature, maintenance, partial shutdown, server replacement, added load and cable rerouting. Datacenters do not live in perfect static conditions. Cables must remain reliable when operations change.

Maintenance And Intervention Safety

Electrical interventions in immersion should be rare, prepared and traceable. Teams must define who can intervene, under which load state, with which lockout procedure, which protective equipment and which return-to-service checks. A power cable should not be moved casually because it blocks a network intervention.

Maintenance should also include visual inspection. Is the jacket intact? Are markings readable? Does the cable remain flexible? Do connectors lock correctly? Is routing still clean? Minor incidents should be recorded because they can reveal progressive incompatibility.

Cyber Resilience And Continuity

Power may seem far from cybersecurity, but it directly affects resilience. A poorly managed outage, unsupervised PDU, cabling error or untracked intervention can cause critical downtime. Logs, electrical supervision and change procedures belong in the governance model.

In cloud or AI platforms, power cables support business services, backups, bastions, GPU clusters and customer environments. Their management must align with continuity requirements. Electrical changes should be planned, approved and auditable.

Qualification Checklist

Before purchase or deployment, ask whether the cable reference is validated with the selected fluid. Does the test temperature and duration match the project? Are connectors included in validation? Do labels resist the fluid? Is the cable section adapted to real load? Does routing respect mechanical constraints? Are lockout and replacement procedures written? Does replacement stock use the same validated reference?

This checklist prevents a common mistake: qualifying tanks and servers, then buying power cables as standard consumables. In immersion cooling, the compatibility chain must be complete.

Mistakes To Avoid

The first mistake is believing dielectric fluid permits electrical compromises. It reduces some risks but never replaces compliant design.

The second mistake is validating a cable without its connectors. The weak point may be the connector plastic, locking mechanism, marking or transition zone.

The third mistake is changing cable reference during maintenance without requalification. A quick substitution can introduce an incompatible jacket or adhesive.

What Matters Most

Power cables in immersion cooling must be treated as infrastructure components, not accessories. Compatibility depends on fluid, materials, connectors, load, temperature, maintenance and traceability.

Readers preparing high-density platforms should require evidence and clear procedures. That rigor is what turns immersion cooling into a reliable production model for cloud, VPS, AI and cybersecurity workloads.

FAQ

Can standard power cables be used in immersion?

Not without validation. The cable, jacket, connectors and markings must be compatible with the exact project fluid.

Does dielectric fluid remove electrical risk?

No. It reduces conduction in normal conditions, but electrical design, protection, lockout and maintenance remain essential.

What should be monitored over time?

Jacket condition, connector locking, label readability, heating, load stability, PDU incidents, cabling changes and replacement-stock conformity.

Sources

  • Open Compute Project, Design Guidelines for Immersion-Cooled IT Equipment: https://www.opencompute.org/documents/design-guidelines-for-immersion-cooled-it-equipment-revision-1-01-pdf
  • Molex, Data Center Power Management Solutions: https://www.molex.com/en-us/industries-applications/power-for-data-center
  • Molex, Data Center Evolution: ORV3 Immersion Cooling Insights: https://www.molex.com/en-us/blog/orv-immersion-cooling-insights
  • ASHRAE TC 9.9, Mission Critical Facilities and Datacom guidance: https://tpc.ashrae.org/?cmtKey=fd4a4ee6-96a3-4f61-8b85-43418dfa988d
Tags:#immersion-cooling#datacenter#voltaneum

Share this article

Related articles

Video: maintaining a server in immersion coolingBlog
August 16, 20267 min

Video: maintaining a server in immersion cooling

A real video shows server maintenance and re-immersion in an immersion cooling tank, with practical notes on hardware compatibility.

Mouhamed BANKOLE
Read more
#datacenter#immersion-cooling#cloud
Network cables for immersion cooling: what to validate before connecting a tankBlog
August 16, 20266 min

Network cables for immersion cooling: what to validate before connecting a tank

Network cables are not accessories in immersion cooling. They shape performance, maintainability and datacenter reliability.

Mouhamed BANKOLE
Read more
Immersion cooling compatible servers: how to qualify hardware before it enters the tankBlog
August 16, 20266 min

Immersion cooling compatible servers: how to qualify hardware before it enters the tank

A practical guide to understanding what makes a server genuinely compatible with immersion cooling, beyond raw GPU density.

Mouhamed BANKOLE
Read more